Global Fire Conventional Panel ORION 2-4-8
- 2, 4 and 8 Zone non-expandable control panels
- Up to 32 conventional smoke and/or heat detectors per Zone
- Active End of Line monitoring
- Programmable non-latching Zones
- Delay timer programmable on/off per Zone
- Coincidence programmable for adjacent Zones
- One man test
- Supervised auxiliary 24 volt output
- 2 Supervised/ monitored sounder circuits
- 3 Remote inputs used for activation of Class Change, Day/Night mode, and Reset
- 2 Relay outputs fire and fault
- Fully EN54 part 2 and 4 compliant
- Repeater output
- Multiplexed output for LEDs and additional relay outputs per zone (GFE-MPX-REL)
- Multiplexed output for sounders per zone (GFE-MPX-SNDR)
- Addressable Loop Interface card (GFE-ADLI)
- 2 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 2
- 4 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 4
- 8 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 8
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
- 2, 4 and 8 Zone non-expandable control panels
- Up to 32 conventional smoke and/or heat detectors per Zone
- Active End of Line monitoring
- Programmable non-latching Zones
- Delay timer programmable on/off per Zone
- Coincidence programmable for adjacent Zones
- One man test
- Supervised auxiliary 24 volt output
- 2 Supervised/ monitored sounder circuits
- 3 Remote inputs used for activation of Class Change, Day/Night mode, and Reset
- 2 Relay outputs fire and fault
- Fully EN54 part 2 and 4 compliant
- Repeater output
- Multiplexed output for LEDs and additional relay outputs per zone (GFE-MPX-REL)
- Multiplexed output for sounders per zone (GFE-MPX-SNDR)
- Addressable Loop Interface card (GFE-ADLI)
- 2 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 2
- 4 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 4
- 8 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 8
TECHNICAL SPECIFICATIONS | |
SUPPLY SPECIFICATION | DETAILS |
PRIMARY SUPPLY VOLTAGE - IN | 230 +10% -15% V AC |
PRIMARY SUPPLY VOLTAGE - OUT | 28.5 V DC nominal |
PRIMARY SUPPLY CURRENT - OUT | 1.7 A @ 28.5 V DC nominal (max.) |
SECONDARY SUPPLY VOLTAGE | 21.0 min. - 27.2 max. V DC - BAT charger o/p 28 V DC |
SECONDARY SUPPLY CURRENT OUTPUT | 1.1 Amp Maximum @ 200C |
INTERNAL BATTERY CAPACITY - MAXIMUM | 2 x 12V x 7Ah Sealed VRLA Lead Acid Batteries |
MAINS FUSE | 4 A -250 V Slow Blow - 20 mm |
BATTERY FUSE | 1.6 Amp - Resettable |
DETECTION CIRCUIT SPECIFICATION | |
NUMBER OF CIRCUITS | 2,4 or 8 |
ZONE CURRENT - QUIESCENT / ALARM | 4 mA / 60 mA - Maximum |
MAX. CABLE RESISTANCE / CAPACITANCE | 40 Ohms / 0.470 uF |
END OF LINE MONITORING | Active EOL - 10uF/50V Bipolar Electrolytic Aluminium Capacitor |
BS-5839 DETECTOR REMOVAL COMPLIANT | YES provided diodes are fitted to detector base |
DEVICES PER ZONE | 32 Maximum - EN54 pt.2 |
ALARM RESISTANCE VALUE | 270 - 1000 Ohms |
SOUNDER CIRCUIT SPECIFICATION | |
CURRENT OUTPUT | 2 outputs w/ 500mA max. current drive per circuit - fully monitored |
ALARM VOLTAGE / END OF LINE RESISTOR | 27.5 V DC Nominal / 10 K Ohms - 1/4 Watt |
AUXILIARY OUTPUTS SPECIFICATION | |
AUXILIARY RELAY OUTPUT | 1 Fire (COM |
RELAY CONTACT RATING | 50 V DC |
REMOTE INPUT SPECIFICATION | |
EVACUATION (CC) - DAY/ NIGHT MODE | Non-Latching |
RESET | Non-Latching |
MECHANICAL & OPERATING SPEC. | |
HUMIDITY | Max 95% RH Non-Condensing |
PROTECTION | IP30 |
OPERATING TEMPERATURE | -10ºC to 50ºC |
WEIGHT | 1.7 Kg - 7 Kg (inc. 2 x 7 AH 12 V bat.) |
DIMENSIONS | 273 (L) x 107 (W) x 404 (H) mm |
COLOUR | Red & White |
Description
ORION
Conventional Fire Detection Panel
The ORION conventional control panel range offers a creatively designed and visually pleasing solution for
smaller cost-conscious projects demanding simplicity of operation. Versions available include 2, 4 and 8 zone
panels and two styles of repeater.
The outstanding programmable features included in this panel range contradict the facilities commonly available
in this type of panel and include: programmable time delay by zone, Day/Night mode, selectable non-latching
zones and coincidence detection.
Operation is extremely intuitive, offering simple control and one-button disablement facilities, as well as the one
man test mode which provides simple and efficient testing of the system.
Advanced configuration solutions include the following: a dedicated RS232 communication interface allowing
connection of up to 4 remote repeater panels, addressable loop interface modules and multiplexed zonal output
relays; giving one of the most highly advanced levels of system integration and compatibility existing on the
market at this level.
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “Global Fire Conventional Panel ORION 2-4-8” Cancel reply
Related Products
-
0 out of 5
Conventional call point DMCL05
Main characteristics
CE certified according to CPD
Conform with the norm EN54-11
Key for reset
Separate key for test
No break glass
Red colour for Alarm status
Yellow colour for extinguishing command
Blue colour for Extinguishing abort -
0 out of 5
Honeywell Gent Conventional Sounder CWSO-RR-S1
- Simple, Fast, Flexible Installation
- Modern design eliminates need for device orientation.
- Designed with full range of common fixing centers.
- Approved to EN54-3.
- Superior sound output and low current consumption.
- 32 tones all approved to EN54-3.
- Suitable for wall and ceiling mount applications.
- Optimised for 12V and 24V systems
- Environmental: RoHS, WEEE
-
0 out of 5
TS1000
Tripod turnstiles are compact and cost-effective entrance solutions. Designing for smooth and silent operation, reducing power consumption, wear and tear. It is suitable for areas with a high traffic.
The TS1000 series, our stainless steel compact version,offer high operating reliability in a small casework, ideal for sites where space is an issue. By receiving a signal from the access control system, or pushing button, it allows the entry of one person in a time. Entering into different directions are electronically controlled. Default mode is to lock the mechanism until a valid authorization signal is received. IIf you want to set one side free, you can adjust the mechanism. In case of emergency, the horizontal arm will drop to allow free passage.
-
0 out of 5
Conventional Sounder VALKYRIE CS
VALKYRIE CS
Conventional Wall Mount Sounder/ Beacon
The VALKYRIE CS is a wall mounted Conventional Sounder/ Beacon with low power consumption. Four different
tones are available and selected using DIL switches 1 and 2.
Both continuous and pulsing outputs are provided via separate negative supply connections allowing for the
presence of differentiated evacuation and alert sounds. -
0 out of 5
Global Fire Addressable Panel JUNO NET
- Fully expandable system from 1-96 Loops with distributed intelligence for added security
- Up to 256 devices per loop (TBA)
- Up to 96 Loop sounders with 32 individually programmable addresses per Loop
- Compatible with major analogue addressable communications protocols
- 2 Fire output changeover relays and 1 Fault output relay (NC)
- Open collector outputs for Fire, Fault and pre-alarm remote indication
- 2 fully monitored sounder outputs on main panel and each sub panel
- Repeaters with optional integrated Sub-Panels (J-NET-REP + Loop Card)
- Redundant network communication via RS485, TCP/IP & Fiber Optics
- 384 programmable zones
- 512 fully programmable sounder and I/O groups
- Event Log 2000 entries FIFO
- Backlit LCD display 4 row * 40 characters
- Multiple programming options, onboard keypad, Remote IR(optional), PS2 Keyboard and GFE Connector software
- Windows™ based PC Graphics package ODYSSEY for alarm management and reporting(Optional)
- Multiple Language support (menu selectable)
- MODBUS (ASCII & RTU) and BMS support
Reviews