Addressable manual call point DMA05
Main characteristics
CE certified according to CPD
Conform with the standards EN54-11, EN54-17, EN54-18
Key for reset
Separate key for test
No break glass
BA9S Waterproof IP65 version
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
Main characteristics
CE certified according to CPD
Conform with the standards EN54-11, EN54-17, EN54-18
Key for reset
Separate key for test
No break glass
BA9S Waterproof IP65 version
Power supply specification
Main supply voltage: 12V to 28Vdc
Nominal main supply voltage 24Vdc
Quiescent current 0.15 ma
Alarm current: 5mA @ 24Vdc
Mechanical characteristics
Unit weight: 170g
Unit dimensions (in mm): 99 x 98 x 49
Unit row material: ABS
Unit colour: Red
Protection class: IP33
Climatic characteristics
Operating temperature: -10°C to +60°C
Storage temperature: +10°C to +50°C
Operating relative humidity: ≤ 93%
Storage relative humidity: ≤ 85%
Description
DMA05 manual call points are devices of transmission of an alarm status towards an addressable indicating panel.
This action is carried out by the operator through mechanical pressure on the window located in the front.
Return to the normal status can be done only after local resetting using a special key.
Moreover the addressable version of manual call point integrates on every device a switch providing the function of line
isolator. This function is assured only in association with the HEPHAIS range panels which are equipped with boards
managing the loop/line. The function “Isolator of line” makes possible the isolation of sections in short-circuit (Shortcircuit
between 2 conductors of the connecting cable), located between 2 devices equipped with switch.
Usually, connection is carried out with shielded cable from 0, 6mm² to 1,5mm². Shield must be protected by an insulator
tape in order to avoid any short-circuit.
Call point also exits in waterproof IP65 version BA95S
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “Addressable manual call point DMA05” Cancel reply
Related Products
-
0 out of 5
Global Fire Conventional Panel ORION 2-4-8
- 2, 4 and 8 Zone non-expandable control panels
- Up to 32 conventional smoke and/or heat detectors per Zone
- Active End of Line monitoring
- Programmable non-latching Zones
- Delay timer programmable on/off per Zone
- Coincidence programmable for adjacent Zones
- One man test
- Supervised auxiliary 24 volt output
- 2 Supervised/ monitored sounder circuits
- 3 Remote inputs used for activation of Class Change, Day/Night mode, and Reset
- 2 Relay outputs fire and fault
- Fully EN54 part 2 and 4 compliant
- Repeater output
- Multiplexed output for LEDs and additional relay outputs per zone (GFE-MPX-REL)
- Multiplexed output for sounders per zone (GFE-MPX-SNDR)
- Addressable Loop Interface card (GFE-ADLI)
- 2 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 2
- 4 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 4
- 8 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 8
-
0 out of 5
D-link 08 port switch Model: DES-1008A
Connectivity
Eight Fast Ethernet LAN ports for high-speed
wired connections
IEEE802.3az EEE Power-saving compliance
D-Link Green Technology features power-saving
by link status and by cable length
Auto-sensing ports automatically detect
network connections and adjust accordingly- Auto-sensing 10/100 Ports
- Auto MDI/MDIX CrossOver
- Flow Control for Secure Transmission
High-speed Wired Connection
Connect up to eight Ethernet devices to enjoy a
high-speed network connection
Plug and Play
Auto MDI/MDIX simplifies cable connections,
allowing for immediate usage and operation
Compact Design
Stylish, compact design can be placed anywhere -
0 out of 5
Honeywell Gent Conventional Smoke Detector : Eco 1003
F E A T U R E S
- Photo-thermal model
- Laser-based remote test unit
- EN 54 Certified (2000 edition)
- Photoelectric, photo-thermal and thermal detectors
- Improved chamber design
- Compatible with fire and security systems
- -20 to +60ºC operating temperature range
- Choice of bases (including a 12V relay version)
- Photoelectric model with integral piezoelectric sounder
(availability subject to further announcement)
-
0 out of 5
HEPHAIS 1600 Addressable Panel
Main characteristics
400 addressable devices
1000 zones, 256 groups of command
Base: 2 loops (200 addr./ loop) or 4 open circuits (32
det./line)
2 programmable inputs / 2 programmable outputs on the
CPU board
2 programmable inputs on the front board
Jbus protocol for remote monitoring software
Detectors management (day/night, scheduled sensitivity,
pre-alarm, alarm confirmation)
Addressable sounders management
Manual/automatic management of monitored sounders line
Download software
Actuators function (activation/deactivation command
groups) -
0 out of 5
Conventional MCP GFE-MCPE
GFE-MCPE
Conventional Manual Call PointThe GFE-MCPE-C is a Conventional Manual Call Point, designed and manufactured to comply with EN54-11,
compatible with all GFE Conventional Control panels. A bi-colour LED flashes Green when the unit is connected to a
control panel and is illuminated Red when in Alarm.
The unit is supplied complete with a hinged flap which protects the trigger element from accidental activation and
reduces malicious activations as two actions are required in order to activate the device. This unit can be both
surface and flush mounted and it can be easily reset using the supplied key after activation.
Reviews