Addressable manual call point DMA05
Main characteristics
CE certified according to CPD
Conform with the standards EN54-11, EN54-17, EN54-18
Key for reset
Separate key for test
No break glass
BA9S Waterproof IP65 version
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
Main characteristics
CE certified according to CPD
Conform with the standards EN54-11, EN54-17, EN54-18
Key for reset
Separate key for test
No break glass
BA9S Waterproof IP65 version
Power supply specification
Main supply voltage: 12V to 28Vdc
Nominal main supply voltage 24Vdc
Quiescent current 0.15 ma
Alarm current: 5mA @ 24Vdc
Mechanical characteristics
Unit weight: 170g
Unit dimensions (in mm): 99 x 98 x 49
Unit row material: ABS
Unit colour: Red
Protection class: IP33
Climatic characteristics
Operating temperature: -10°C to +60°C
Storage temperature: +10°C to +50°C
Operating relative humidity: ≤ 93%
Storage relative humidity: ≤ 85%
Description
DMA05 manual call points are devices of transmission of an alarm status towards an addressable indicating panel.
This action is carried out by the operator through mechanical pressure on the window located in the front.
Return to the normal status can be done only after local resetting using a special key.
Moreover the addressable version of manual call point integrates on every device a switch providing the function of line
isolator. This function is assured only in association with the HEPHAIS range panels which are equipped with boards
managing the loop/line. The function “Isolator of line” makes possible the isolation of sections in short-circuit (Shortcircuit
between 2 conductors of the connecting cable), located between 2 devices equipped with switch.
Usually, connection is carried out with shielded cable from 0, 6mm² to 1,5mm². Shield must be protected by an insulator
tape in order to avoid any short-circuit.
Call point also exits in waterproof IP65 version BA95S
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “Addressable manual call point DMA05” Cancel reply
Related Products
-
0 out of 5
Global Fire Addressable Panel JUNO NET
- Fully expandable system from 1-96 Loops with distributed intelligence for added security
- Up to 256 devices per loop (TBA)
- Up to 96 Loop sounders with 32 individually programmable addresses per Loop
- Compatible with major analogue addressable communications protocols
- 2 Fire output changeover relays and 1 Fault output relay (NC)
- Open collector outputs for Fire, Fault and pre-alarm remote indication
- 2 fully monitored sounder outputs on main panel and each sub panel
- Repeaters with optional integrated Sub-Panels (J-NET-REP + Loop Card)
- Redundant network communication via RS485, TCP/IP & Fiber Optics
- 384 programmable zones
- 512 fully programmable sounder and I/O groups
- Event Log 2000 entries FIFO
- Backlit LCD display 4 row * 40 characters
- Multiple programming options, onboard keypad, Remote IR(optional), PS2 Keyboard and GFE Connector software
- Windows™ based PC Graphics package ODYSSEY for alarm management and reporting(Optional)
- Multiple Language support (menu selectable)
- MODBUS (ASCII & RTU) and BMS support
-
0 out of 5
Global Fire Conventional Panel ORION 2-4-8
- 2, 4 and 8 Zone non-expandable control panels
- Up to 32 conventional smoke and/or heat detectors per Zone
- Active End of Line monitoring
- Programmable non-latching Zones
- Delay timer programmable on/off per Zone
- Coincidence programmable for adjacent Zones
- One man test
- Supervised auxiliary 24 volt output
- 2 Supervised/ monitored sounder circuits
- 3 Remote inputs used for activation of Class Change, Day/Night mode, and Reset
- 2 Relay outputs fire and fault
- Fully EN54 part 2 and 4 compliant
- Repeater output
- Multiplexed output for LEDs and additional relay outputs per zone (GFE-MPX-REL)
- Multiplexed output for sounders per zone (GFE-MPX-SNDR)
- Addressable Loop Interface card (GFE-ADLI)
- 2 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 2
- 4 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 4
- 8 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 8
-
0 out of 5
HEPHAIS 1600 Addressable Panel
Main characteristics
400 addressable devices
1000 zones, 256 groups of command
Base: 2 loops (200 addr./ loop) or 4 open circuits (32
det./line)
2 programmable inputs / 2 programmable outputs on the
CPU board
2 programmable inputs on the front board
Jbus protocol for remote monitoring software
Detectors management (day/night, scheduled sensitivity,
pre-alarm, alarm confirmation)
Addressable sounders management
Manual/automatic management of monitored sounders line
Download software
Actuators function (activation/deactivation command
groups) -
0 out of 5
Honeywell Gent Conventional Heat Detector : Eco 1005
• Low current draw, Low profile design
• 580C operating temperature
• Operates at 12 and 24VDC
• Remote alarm test feature
• Easy Maintenance
• Range of detector bases available
• Remote LED Option
• Approved to EN54 –5:2000 Class A1R
• Approved to MED 96/98/EC (Amendment 2009/26/EC)
• Extended warranty -
0 out of 5
Honeywell Gent Conventional MCP
- Fully compliant with EN54, Part 11
- Re-settable operating element option
- Weather proof IP67
- Semi-flush or surface mounting
- 470 Ohm resistor and Normally Open
contact complete with glass - Resistive and clean contact connections
- Standard MCP, surface mounted
Reviews