Conventional Smoke Detector (SD3) OC05
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
12V version
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
12V version
Power supply specification
Main supply voltage: 13Vdc to 27 Vdc
Nominal main supply voltage: 20 Vdc
Quiescent current (20 Vdc): 25µA
Alarm current (20 Vdc): 32ma
Power Down Reset Time: >4s
Remote alarm indicator output: 0V in standby / 3,3Vdc in alarm
Mechanical characteristics
Unit weight: 130g
Unit dimensions (in mm): H:55 D:104
IP index: IP 32
Unit row material: ABS
Unit colour: White
Mounting mode: Base
Fixing - distance between centres: 50mm to 60mm
under ceiling: 2 screws Ø 4
Climatic characteristics
Operating temperature: -10°C to +60°C
Storage temperature: +10°C to +50°C
Operating relative humidity: ≤ 93%
Storage relative humidity: ≤ 85%
Description
STANDARD EN54-7 Ed2000 / Full CE marking according to CPD
Number of certification: 0333 CPD 075 013
The Optical smoke detector analyzes an atmosphere by reflection of a light on the particles of smoke
according to TYNDALL effect. It detects especially the cold and visible smoke particles (0,3µm to 2µm)
produced in the early stages of a fire. The threshold of response of alarm is regulated to obtain the value
m=0,2db/m±0,03 according to standard EN54-7.
OC05 includes a developed technology (microprocessors, smd components) which means precision and
high reliability. A specific head detection fixed by a single ceiling base.
12V version of OC05 detectors is also available for security type systems
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “Conventional Smoke Detector (SD3) OC05” Cancel reply
Related Products
-
0 out of 5
Honeywell Gent Conventional MCP
- Fully compliant with EN54, Part 11
- Re-settable operating element option
- Weather proof IP67
- Semi-flush or surface mounting
- 470 Ohm resistor and Normally Open
contact complete with glass - Resistive and clean contact connections
- Standard MCP, surface mounted
-
0 out of 5
Addressable Indoor sounder AVSA05R
Main characteristics
Addressable independent device
Loop powered
90 dB (+/- 3 dB) at 1 meter
6 tones selectable
Integrated loop isolator
Red or white color
Lateral hearings
Volume control -
0 out of 5
Global Fire Conventional Panel ORION 2-4-8
- 2, 4 and 8 Zone non-expandable control panels
- Up to 32 conventional smoke and/or heat detectors per Zone
- Active End of Line monitoring
- Programmable non-latching Zones
- Delay timer programmable on/off per Zone
- Coincidence programmable for adjacent Zones
- One man test
- Supervised auxiliary 24 volt output
- 2 Supervised/ monitored sounder circuits
- 3 Remote inputs used for activation of Class Change, Day/Night mode, and Reset
- 2 Relay outputs fire and fault
- Fully EN54 part 2 and 4 compliant
- Repeater output
- Multiplexed output for LEDs and additional relay outputs per zone (GFE-MPX-REL)
- Multiplexed output for sounders per zone (GFE-MPX-SNDR)
- Addressable Loop Interface card (GFE-ADLI)
- 2 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 2
- 4 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 4
- 8 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 8
-
0 out of 5
Honeywell Gent Conventional Sounder CWSO-RR-S1
- Simple, Fast, Flexible Installation
- Modern design eliminates need for device orientation.
- Designed with full range of common fixing centers.
- Approved to EN54-3.
- Superior sound output and low current consumption.
- 32 tones all approved to EN54-3.
- Suitable for wall and ceiling mount applications.
- Optimised for 12V and 24V systems
- Environmental: RoHS, WEEE
-
0 out of 5
Conventional Sounder VALKYRIE CS
VALKYRIE CS
Conventional Wall Mount Sounder/ Beacon
The VALKYRIE CS is a wall mounted Conventional Sounder/ Beacon with low power consumption. Four different
tones are available and selected using DIL switches 1 and 2.
Both continuous and pulsing outputs are provided via separate negative supply connections allowing for the
presence of differentiated evacuation and alert sounds.